CDU Installation Guide Page 29
Cooling Distribution Unit
OPERATION (continued)
(change pump from 1 to 2 or 2 back to 1 – OK to initialise)
(change valve from 1 to 2 or 2 back to 1 – OK to initialise)
(no automatic function - for full manual control of all functions)
Automatic / Manual (set unit to manual or automatic operation)
0000000000 (manually set digital output status – see Section 5.8)
0 to 100 % (manually set pump speed)
0 to 100 % (manually set valve 1 position)
0 to 100 % (manually set valve 2 position)
(for manual control of some functions while still running in automatic mode)
4-4-1-1 P1 inverter (set pump speed)
4-4-1-2 P2 inverter (set pump speed)
4-4-1-3 P1 DOL (switch to Manual for ON)
4-4-1-4 P2 DOL (switch to Manual for ON)
4-4-2-1 Valve 1 (set valve position)
4-4-2-2 Valve 2 (set valve position)
Automatic/Manual (switch to Manual for ON)
Automatic/Manual (simulate fault on customer warning relay)
Automatic/Manual (simulate fault on customer alarm relay)
(resets alarm delay timer (scr.6-7) to stop nuisance alarms breaking through
screens during manual overrides – OK to initialise)
(set pump 1 run hours to zero – OK to initialise)
(set pump 2 run hours to zero – OK to initialise)
(set valve 1 run hours to zero – OK to initialise)
(set valve 2 run hours to zero – OK to initialise)
(set all pump & valve run hours to zero – OK to initialise)
Default 24 Hours [adj. 24, 48. 72 hrs] (set alarm defer period)
dd/mm/yy hh:mm:ss (set date & time - 24 hour clock)
Europe, Manual, No DST or N. America
Default 0.5 Bar [adj. 0.5 to 1 bar] (shut off threshold for fill pump)
Default 3 mins [adj. 1 to 15 mins] (run time for float switch to make or fill
pressure to be achieved, prior to alarm)
Default 4 secs [adj. 1 to 30 secs] (reservoir float switch de-bounce time)
DP setpoints
(pump differential
pressure set points for
pump speed control
loop)
6-2-2-1 Sys diff 1 RDHx – Default 2.1 Bar [adj. 0.5 to 4 bar]
6-2-2-2 Sys diff 2 RDHx – Default 2.3 Bar [adj. 0.5 to 4 bar]
6-2-2-3 Sys diff 3 RDHx – Default 2.5 Bar [adj. 0.5 to 4 bar]
6-2-2-4 Sys diff 4 RDHx – Default 2.7 Bar [adj. 0.5 to 4 bar]
6-2-2-5 Sys diff 5 RDHx – Default 2.9 Bar [adj. 0.5 to 4 bar]
6-2-2-6 Sys diff 6 RDHx – Default 3.1 Bar [adj. 0.5 to 4 bar]
Default 10 [adj. 5 to 120 secs] (scan period for pump speed control loop)
Default 0.5 Bar [adj. 0.1 to 3 bar] (threshold for pump low flow alarm)